Error Events Table

CodeDetailsCorrective ActionsRelated Parameter
E001 By the load and the operating conditions, overcurrent has occurred - If the acceleration is fast, increase the acceleration time [AC120]
- Use the overcurrent suppression function [DA112]
- Use the overload restriction function [BA122]
- Use the overcurrent retry function [BA122]
- In order to stabilize the control, adjust the constant [HA-01]
AC120, DA112, BA122, BA122, HA-01
E005 / E039 By the load and the operating conditions, current has increased - If the acceleration is fast, increase the acceleration time [AC120]
- Use the overload restriction function [BA122]
- If the motor sound is abnormal, in order to stabilize the control, adjust the constant [HA-01]
AC120, BA122, HA-01
E006 Braking resistor use is limited - If the deceleration is fast, increase the deceleration time [AC121]
- Reselection of the braking resistor is necessary [DA-20]
AC121, DA-20
E007 Internal voltage has increased. Insufficient capacity of the inverter - If the deceleration is fast, increase the deceleration time [AC121]
- Use the overvoltage suppression functions [DA140][DA146]
- Use the overvoltage retry function [BB-23]
- Use a braking option
AC121, DA140/DA146, BB-23
E008 Main CPU abnormality - Carry out counter measures for the inverter noise
- Consecutive error may cause a failure
-
E009 Main circuit supply has drop - To disable the undervoltage error, change setting [BB-27]
- Use the undervoltage retry function [BB-21]
BB-27, BB-21
E010 Current detector abnormality - Carry out counter measures for the inverter noise
- Consecutive error may cause a failure, replacement of the components is necessary
-
E012 [EXT] input terminal is ON - Check the signal status of the input terminal [DA-51]
- Check if there are no operations by communication or programme
DA-51
E013 [USP] input terminal is ON if at the start-up, the RUN command was issued right at the start up - Make sure that an operation command is not introduced at the time of turning ON the inverter [DA-51] DA-51
E014 Ground fault detected at main circuit voltage turning-on - Check for ground fault of the motor, wiring, etc. -
E015 Continued state of incoming high power - Review the power circumstances, such as the power supply capacity [DA-40] DA-40
E016 Instantaneous power failure, control supply has dropped - If you wish to avoid the tripping, use the power loss retry function [BB-20] BB-20
E019 Abnormality in temperature detector circuit - Carry out counter measures for the inverter noise
- Consecutive errors may cause a failure
-
E020 Because of cooling-fan life span, internal temperature has increased - Change of the cooling-fan is necessary
- Lower the carrier frequency [BB101]
BB101
E021 Internal temperature has increased - Requires a review of the installation circumstances
- Lower the carrier frequency
-
E024 Disconnection of the wiring in the supply side has occurred - Check the fastening of the input wiring with screws
- Check that the 3 phases are correctly inserted
-
E030 Suddenly current increase - Output ground fault - Disconnection confirm
- Check that the motor is not locked
-
E034 Disconnection of the wiring in the motor side has occurred - Check the output wiring disconnection, motor insulation failure, etc.
- Check that the 3 phases are correctly inserted
-
E035 Abnormal motor temperature - Improve the motor cooling circumstances
- Use the overload restriction function [BA122]
BA122
E036 Thermistor abnormality - Check for the break-down of the thermistor [CB-40]
- Check the thermistor settings [DA-51]
CB-40, DA-51
E036 Brake abnormality - Check for the break-down of the brake and for the disconnection of the wiring for the [BOK] signal
- Check the brake waiting time [AF134][AF141]
AF134/AF141
E038 During slow speed, current has increased - If torque is needed during slow speed, a review of the inverter capacity is necessary -
E040 Panel disconnection error - Check for the disconnection of the panel from the inverter [UA-20]
- Noise counter-measures are necessary
UA-20
E041 RS485 communication error - Noise counter-measures are necessary
- Check the communication setting [CF-01]
CF-01
E042 RTC error - Battery replacement for the panel is necessary -
E043 ~ E045 / E050 ~ E059 There is an error in the EzSQ programme - For more information, please refer to the user’s guide. -
E060 ~ E089 There is an error in the option - For more information, please refer to each option in user’s guide. -
E090 ~ E096 There is an error in the STO path - For more information, please refer to the P1 functional safety guide. -

 


Note:

  • For other errors not shown above, refer to the user’s guide.
    1. STO function is not suitable for SH1 series.
  • Regarding the warnings, please refer to the user’s guide. Fixing the parameter details shown in the panel screen may end the warning.

 

 

2. 기본적인 조치 방법
대부분의 알람 및 에러는 아래 조치로 해결이 가능합니다:

파라미터 재설정
드라이버 리셋
전원 재인가 (전원 껐다 켜기)
※ 단, 위의 조치로 해결되지 않는 경우 현장에서는 추가적인 대응이 어렵습니다.

3. 하드웨어 관련 설정 및 정밀 점검

하드웨어적인 문제나 고급 설정이 필요한 경우, 엠이티(MET)로 수리 의뢰해 주시기 바랍니다.
현장에서 무리한 수정을 시도하는 것은 장비 손상의 원인이 될 수 있습니다.

HITACHI SH1 English Manual.pdf
7.24MB

 

📞 기술 문의 / 수리 접수

해당 장비의 수리, 유지보수 또는 기술 문의는
M.E.T 고객센터 1670-8257 또는 이메일 repair@met.kr 로 연락 주세요.

 

사업자 정보 표시펼치기/접기
주식회사 엠이티 | 김영삼 | 대전광역시 유성구 테크노11로 46 | 사업자 등록번호 : 314-86-33419 | TEL : 042-934-8257 | 통신판매신고번호 : 제 2014-대전유성-0334호 | 사이버몰의 이용약관 바로가기